Standards:
- Nationals: NF C 33-210
Usage description:
- Single-phase and three-phase service cables, with telereport
- Low voltage underground insulated cables NF C 33-210 for public connection networks, with TeleReference cables.
Characteristics:
- Core: round, massive aluminum , 2x2x0.6 mm.
- Insulation: PVC
- Assembly: in four.
- Screen: aluminum / polyester with continuity wire.
- Sheath: PVC.
- Operating voltage: 0.6 / 1 kV.
- Test voltage: 3.5 kV alternating for 15 minutes
- Resistance to shock waves: 1.2 / 50 μs of a positive or negative polarity with a peak value of 20 Kv
- The indicated intensities are determined according to standard NF C 33-210 appendix F: buried cable at 0.8 m used in a three-phase circuit for a ground temperature of 20 ° C and a thermal resistivity of the ground of 1 K.m / W.
Standards:
- Nationals: NF C 33-210
Usage description:
Low voltage underground insulated cables NF C 33-210 for public distribution networks, 3 phases + neutral.
Phase conductors are wired aluminum (class 2), sectoral or round.
The neutral conductor is made of wired aluminum (class 2), round and lead-wrapped.
The sealing between the lead sheath and the core of the neutral conductor is insured by a water-repellent material.
Sheath: on request, anti-termite treatment possible.
Characteristics
- Insulation: XPLE
- Outer sheath: PVC
- Conductor nature: Aluminum or Copper.
- Screen: Two galvanized mild steel tapes with cover.
- Number of phases: 3
- Ecru PVC jam only for 50 mm².
- Test voltage: 3.5 kV alternating for 15 minutes,
- Shock resistance: 1.2 / 50 μs of positive or negative polarity with a peak value of 20 kV